Safety engineering, Safe bus interfaces profisafe connection – Lenze E94AYAE SM301 User Manual

Page 97

Advertising
background image

Safety engineering

Safe bus interfaces

PROFIsafe connection

1

l

97

EDS94AYAE EN 7.0

Bit coding of PROFIsafe input data

Bit

Name

Description

0

STO active

The STO function is active and the drive is safely switched to torque−free
operation.
This bit is also set at the end of the stopping time by SS1.

1

SS1 active

The SS1 function is active.
At the end of the function the STO bit is set.

2

SS2 active

The SS2 function is active.
At the end of the function the SOS bit is set.

3

SLS1 active

The SLS1 function is active.
When the braking time has elapsed, the SLS1_monitored bit is set
additionally.

4

SLS2 active

The SLS2 function is active.
When the braking time has elapsed, the SLS2_monitored bit is set
additionally.

(From SM301 V1.1 onwards)

5

SLS3 active

The SLS3 function is active.
When the braking time has elapsed, the SLS3_monitored bit is set
additionally.

(From SM301 V1.1 onwards)

6

SLS4 active

The SLS4 function is active.
When the braking time has elapsed, the SLS4_monitored bit is set
additionally.

(From SM301 V1.1 onwards)

7

SDIpos is active

The SDIpos function is active.
After the deceleration time has expired, bit 21 (SDIpos monitored) is set in
addition.

(As of SM301 V1.3)

8

SDIneg is active

The SDIneg function is active.
After the deceleration time has expired, bit 22 (SDIneg monitored) is set in
addition.

(As of SM301 V1.3)

9

ES active

1: ES function in special operation is active: Motion function
0: ES function in special operation is not active: Stop function

10

SLI is active

The safely limited increment (SLI) function is active.

(As of SM301 V1.4)

11

OMS

1: special operation requested
0: normal operation

16

SOS monitored

The SOS function is monitored.

17

SLS1 monitored

The SLS1 function is monitored.

18

SLS2 monitored

The SLS2 function is monitored.

(from SM301 V1.1)

19

SLS3 monitored

The SLS3 function is monitored.

(from SM301 V1.1)

20

SLS4 monitored

The SLS4 function is monitored.

(from SM301 V1.1)

21

SDIpos is monitored

The SDIpos function is active, the compliance with the direction of
movement is monitored.

(As of SM301 V1.3)

22

SDIneg is monitored

The SDIneg function is active, the compliance with the direction of
movement is monitored.

(As of SM301 V1.3)

23

SSE active

The SSE function is monitored.
When the stopping time has elapsed, the STO or SS1 bit is set according to
the emergency stop function parameterised.

24

SD−In1

Sensor at I1A and I1B

Channels A and B are in the ON state

25

SD−In2

Sensor at I2A and I2B

Channels A and B are in the ON state

26

SD−In3

Sensor at I3A and I3B

Channels A and B are in the ON state

27

SD−In4

Sensor at I4A and I4B

Channels A and B are in the ON state

29

OMS active

Special operation is not active.

(from SM301 V1.1)

31

Error active

Error status (i.e trouble or warning) is active.

Tab. 1−12

Detailed specification of the PROFIsafe input data