Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

109

Safe Maximum Speed and Direction Monitoring

Chapter 9

Figure 45 - Positive Safe Direction Monitoring Timing Diagram

Figure 46 - Negative Safe Direction Monitoring Timing Diagram

If motion is detected in the incorrect direction while Safe Direction Monitoring
is active, a Direction fault occurs. If a Direction fault is detected while the drive is
monitoring motion, the configured [Stop Category] is initiated and direction
monitoring is not performed during the safe stop. If a Direction fault is first
detected after the initiation of the safe stop, then all outputs go to their faulted
state.

For more information about faults, see

Fault Reactions

on

page 137

.

0

300

Speed

Safe Direction Fault

Time

Safe Direction

0

-300

Speed

Time

Safe Direction

Safe Direction Fault