Safety Configuration Example

Chapter 11

Configure the Safe Stop Tab Parameters

Refer to

Appendix B

beginning on

page 145

for default, minimum, and

maximum values for these safety parameters.

Follow these steps to configure the Safe Stop tab parameters.

1. Expand the Safety folder to gain access to the Safe Stop tab.

2. Under Safety Configuration, choose Safe Stop.

The Safe Stop tab opens.

3. From the Stop Category pull-down menu, choose Safe Torque-Off

(default) and check the Standstill Checking box, as the parameter value.

Safe Torque-Off with Standstill Checking removes motion generated
power from the motor immediately after an
E-Stop command and unlocks the door when Standstill Speed is detected.

4. Enter the desired [Maximum Stop Time] parameter value.

5. Enter the desired [Standstill Speed] parameter value.

6. Enter the desired [Standstill Position Window] parameter value.

TIP

If a rotary feedback device is used, the units are revolutions per minute
(RPM). If a linear feedback device is used, the units are in millimeters per
second (mm/s).