Chapter 7

Safe Limited Speed (SLS) Modes

Safe Stop Reset (SS Reset) and Safe Limited Speed Reset (SLS Reset)

The door must be closed when an SS Reset or SLS Reset is requested. An SS
Reset results in a Door Monitoring fault if the door is open when the reset is
requested by a transition of the SS_In input from OFF to ON. An SLS Reset also
results in a Door Monitoring fault if the door is open when the reset is requested
by a transition of the SLS_In input from OFF to ON. A Door Monitor fault is a
Stop Category fault that initiates the configured [Stop Category].

If an SS Reset is attempted while the SLS_In input is OFF, an ESM Monitoring
fault occurs. An ESM Monitoring fault is a Stop Category fault that initiates the
configured [Stop Category].

SLS with Door Monitoring
and Enabling Switch
Monitoring Parameter List

To configure the drive for Safe Limited Speed with Door Monitoring and
Enabling Switch Monitoring, set the [Door Monitor] and [Enable Switch
Monitor] parameters in addition to the Safe Stop parameters listed on

page 66

and the Safe Limited Speed parameters listed on

page 74

.

Table 25 - SLS with Door Monitoring and Enabling Switch Monitoring Parameters

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Safety
Change System
Configuration

Operation Mode

Defines the primary operating mode of the speed
monitoring safety functions.

Setting:

SafeStop-Safe Limited Speed with Door Monitor and
Enabling Switch

Input
Change Input
Configuration Type

Door Monitor

Configuration for the Door Monitor input (DM_In).

Default:

Not Used

(1)

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel

Enabling Switch
Monitor

Configuration for the Enabling Switch input (ESM_In).

Default:

Not Used

(1)

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel

(1) You must configure this parameter with a non-zero value in this mode.