Door control output (dc_out) – Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual

Page 38

Advertising
background image

38

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Chapter 4

Speed Monitoring I/O Signals

Door Control Output (DC_Out)

You can use this output for door control in single-axis and multi-axis systems.
This output attempts to maintain last state when a fault occurs.

The DC_Out output is updated based on door control logic status, the [Door
Control Output] parameter setting, and any Safe State faults that can be
detected.

This output is Unlocked only when motion is verified to be at Standstill Speed or
Safe Limited Speed.

Figure 8 - Door Control and Lock Monitoring

If an error is detected on either channel of the dual-channel output, a fault occurs.
I/O faults are Stop Category faults that initiate the configured Stop Category.
The fault is latched until the drive is successfully reset.

For more information on faults, refer to

Chapter 12

.

The DC_Out output can be used as a bipolar output in Power to Release or
Power to Lock configurations, or it can be configured as Cascading (2Ch
Sourcing).

TEST_OUT_CH0

DM_IN_CH0

DM_IN_CH1

LM_IN_CH0

LM_IN_CH1

DC_OUT_CH1

DC_OUT_CH0

Door Status

Locking Mechanism Status

TEST_OUT_CH1

TEST_OUT_CH0

TEST_OUT_CH1

IOD-27

IOD-28

IOD-27

IOD-28

IOD-31

IOD-32

IOD-33

IOD-34

IOD-36

IOD-35

TIP

Check your interlock switch for internal jumpers before installation.