Chapter 11

Safety Configuration Example

Configure Safe Limited Speed Tab Parameters

Refer to

Appendix B

beginning on

page 145

for default, minimum, and

maximum values for these safety parameters.

Follow these steps to configure the Safe Limited Speed tab parameters.

1. Expand the Safety folder to gain access to the Safe Limited Speed tab.

2. Under Safety Configuration, choose Safe Limited Speed.

The Safe Limited Speed tab dialog box opens.

3. Enter the desired [Safe Limited Speed Monitor Delay] parameter value.

4. Enter the desired [Safe Limited Speed] parameter value.

TIP

If a rotary feedback device is used, the units are revolutions per minute
(RPM). If a linear feedback device is used, the units are in millimeters per
second (mm/s).