General Device and Feedback Monitoring Configuration

Chapter 5

Feedback Voltage Monitoring Range

Use the [5V Monitoring] and [9V Monitoring] parameters to set the feedback
voltage monitoring range. The monitoring ranges help define the trip zone for
encoder 1 and encoder 2, respectively.

Table 17 - Feedback Voltage Monitoring Range

Your power supply must stay within the No Trip range.

Feedback Fault

The allowable frequency of feedback input signals is limited. The drive monitors
feedback signals whenever its configuration is valid and the Operation mode is
not configured as Disabled.

Table 18 - Maximum Encoder Frequency

If the feedback signals indicate greater-than or equal-to the maximum value, a
Feedback_

x fault (Safe State fault) occurs (x equals 1 or 2 depending upon the

encoder that has the fault).

Diagnostics are performed on the encoder input signals. If the encoder diagnostic
tests fail, a Feedback_

x fault (Safe State fault) occurs.

5/9V Monitoring
Setting

5

9

Range

4.5…5.5V

7…12V

Trip Zone

< 4.5V

< 7V

The encoder must be specified

Can Trip

4.5…4.62V

7…7.4V

to operate across this complete

No Trip

4.62…5.38V

7.4…11.4V

range or larger.

Can Trip

5.38…5.5V

11.4…12.0V

Trip Zone

>5.5V

> 12.0V

Encoder Type

Frequency, max

Sine/cosine

≤ 100 kHz

Incremental

≤ 200 kHz