Specifying the safety configuration – Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual

Page 115

Advertising
background image

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

115

Safety Configuration and Verification

Chapter 10

Specifying the Safety Configuration

You must create a specification for the system configuration that addresses the
safety requirements identified by a risk assessment of your application. Use the
specification to verify that the configuration is selected correctly and that it fully
addresses your application’s functional and safety control requirements. The
specification must be a detailed description that can include (if applicable):

a sequence of operations.
flow and timing diagrams.
sequence charts.
a configuration description of each parameter.
documented descriptions of the steps with step conditions and actuators to

be controlled.

input and output definitions.
I/O wiring diagrams and references.
a theory of operation.
a matrix or table of stepped conditions and the actuators to be controlled,

including sequence and timing diagrams.

a definition of marginal conditions, for example, operating modes.

The I/O portion of the specification must contain the analysis of field circuits,
that is, the type of sensors and actuators.

Sensors (Digital or Analog)

Signal in standard operation (dormant current principle for digital

sensors, sensors OFF means no signal)

Determination of redundancies required for SIL levels
Discrepancy monitoring and visualization, including your diagnostic

logic

Actuators

Position and activation in standard operation (normally OFF)
Safe reaction/positioning when switching OFF or power failure.
Discrepancy monitoring and visualization, including your diagnostic

logic.