Table 13 - Encoder Resolution 5000 lines/mm

Table 14 - Encoder Resolution 20,000 lines/mm

For example, an encoder resolution of 128 and Overspeed Response Time of
42 ms results in a speed resolution accuracy of ±19.865 RPM if your Safe
Maximum Speed is configured for 100.0 RPM. An SMS Speed fault can occur
when encoder 1 is at 80.135 RPM. However, the SMS Speed fault cannot occur
until encoder 1 reaches 119.865 RPM.

Figure 11 - Need Figure Title Here

Overspeed Response Time
Setting

Speed (mm/s)

0.01

0.1

1

10

40

42

0.008367

0.008667

0.011667

0.041667

0.141667

48

0.004183

0.004333

0.005833

0.020833

0.070833

60

0.002092

0.002167

0.002917

0.010417

0.035417

84

0.001046

0.001083

0.001458

0.005208

0.017708

132

0.000523

0.000542

0.000729

0.002604

0.008854

228

0.000261

0.000271

0.000365

0.001302

0.004427

420

0.000131

0.000135

0.000182

0.000651

0.002214

Overspeed Response Time
Setting

Speed (mm/s)

0.01

0.1

1

10

42

0.002117

0.002417

0.005417

0.035417

48

0.001058

0.011208

0.002708

0.017708

60

0.000529

0.000604

0.001354

0.008854

84

0.000265

0.000302

0.000677

0.004427

132

0.000132

0.000151

0.000339

0.002214

228

0.000066

0.000076

0.000169

0.001107

420

0.000033

0.000038

0.000085

0.000553

119.865

100

80.135

RPM

Trip Zone

Can Trip

No Trip