Chapter 3

Installation and Wiring

Power Supply Requirements

The external power supply must conform to the Directive 2006/95/EC Low
Voltage, by applying the requirements of EN61131-2 Programmable Controllers,
Part 2 - Equipment Requirements and Tests and one of the following:

EN60950 - SELV (Safety Extra Low Voltage)
EN60204 - PELV (Protective Extra Low Voltage)
IEC 60536 Safety Class III (SELV or PELV)
UL 508 Limited Voltage Circuit
21.6…28.8V DC must be supplied by a power supply that complies with

IEC/EN60204 and IEC/EN 61558-1.

For planning information, refer to the guidelines in Industrial Automation
Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

.

Wiring the Safety
Connections

Safety connections are made by using the 2090-K6CK-D44M low-profile
connector kit.

Figure 2 - Making Safety Connections

Refer to the Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drive
User Manual, publication

2094-UM002

, for safety, auxiliary feedback, and I/O

signal descriptions and wiring examples when using the 2090-K6CK-D44M
connector kit.

28 27 26 25 24 23 22 21 20 19 18 17 15 14 0

AUX FEEDBACK

0 11 10 9 8 7 6 5 4 3 2 1

0 39 41 40 39 42 40 39 43 40 39 44 40

INPUTS

0 38 37 36 35 34 33 32 31 30 29

28 27 28 27 28 27 28 27

S1 ONL

Y

S1 ONL

Y

S0&S1 W/S0 DISABLED

28 27 26 25 24 23 22 21 20 19 18 17 15 14 0

AUX FEEDBACK

0 11 10 9 8 7 6 5 4 3 2 1

0 39 41 40 39 42 40 39 43 40 39 44 40

INPUTS

0 38 37 36 35 34 33 32 31 30 29

28 27 28 27 28 27 28 27

S1 ONL

Y

S1 ONL

Y

S0&S1 W/S0 DISABLED

Clamp

2090-K6CK-D44M
Low-profile Connector Kit

Use tie wraps (4x)

for stress relief.

Turn clamps over for smaller

diameter cables.

Aux Feedback and I/O

Wires and Cables

Safety Wires

and Cables

Use shield clamps (3x) for

high-frequency bonding.

Kit pin numbering corresponds to the IOD

connector. Pins 27, 28, 39, and 40 are

given multiple terminals to

accommodate additional connections.