Parameters and Settings in a
Linear List

This table lists the configurable parameters and their valid settings. If any values
other than those listed in the table are configured for any of the parameters, an
Invalid Configuration fault occurs.

Table 41 - Configurable Parameters and Settings

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Safety Main
Commands

Password

Safety configuration password is optional, but once set
is required to use Safety Main tab commands.

Range:

N/A

Safety Lock Status

Status indicator for the safety configuration lock/unlock
status.

Default:

Unlocked

Options:

Unlocked
Locked

Safety Main
Configuration
Signature

Configuration
Signature ID

Safety configuration identifier (read only). Signature ID
is written when the Apply command is used
successfully.

Range:

N/A

Safety
Change System
Configuration

System Configuration

Defines whether the drive is a single unit or if it occupies
a first, middle, or last position in a multi-axis cascaded
system.

Default:

Single Unit

Options:

Single Unit
Cascaded First Unit
Cascaded Middle Unit
Cascaded Last Unit

Operation Mode

Defines the primary operating mode of the speed
monitoring safety functions.

Default:

SafeStop

Options:

Disabled
SafeStop
SafeStop-DoorMonitor
SafeStop-SafeLimitedSpeed
SafeStop-SafeLimitedSpeed-DoorMonitor
SafeStop-SafeLimitedSpeed-EnableSwitch
SafeStop-SafeLimitedSpeed-DoorMonitor-EnableSwitch
SafeStop-SafeLimitedSpeedStatusOnly

Reset Type

Defines the type of reset used by the drive.

Default:

Manual Monitored

Options:

Automatic
Manual
Manual Monitored

Door Control Output

Defines the lock and unlock state for door control output
(DC_Out).
Any Door Control Output option can be used for a
single-axis system or for the last unit in a multi-axis
system. The first and middle units of a multi-axis system
must be configured as 2 Channel Sourcing.

Default:

Power to Release

Options:

Power to Release
Power to Lock
2 Channel Sourcing

Enable Lock
Monitoring

Lock Monitoring can be enabled only when the drive is a
single unit or as the first unit in a multi-axis system as
set in [System Configuration].

Default:

Lock Monitoring Not Enabled

Options:

Lock Monitoring Not Enabled
Lock Monitoring Enabled

Overspeed Response
Time

Configuration for the feedback interface sampling rate.

Default:

42 ms

Options:

42 ms
48 ms
60 ms
84 ms
132 ms
228 ms
420 ms