Troubleshooting the Safe Speed Monitoring Drive

Configuration Fault Example

Configuration faults are not displayed on the drive. However, you can use the
Safety Configuration Tool to access the fault code. Press Apply to see if a
configuration fault exists.

In this configuration fault example, an invalid Velocity Ratio setting caused
Configuration Fault 33. Refer to the table on

page 141

for a complete list of all

configuration fault codes and descriptions.

Figure 51 - Feedback Tab - Configuration Fault 33