Page 76

Advertising
background image

76

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Chapter 7

Safe Limited Speed (SLS) Modes

If Safe Limited Speed Monitoring is active (SLS_In input is OFF) and the drive
has verified a safe speed condition, the door can be unlocked and opened.

You can monitor the door’s status with or without the door control (lock/
unlock) function. When door control logic is set to lock, it prevents personnel
from entering the hazardous area when the machine is not at a safe speed or at
Standstill Speed.

Safe Limited Speed Reset

When properly configured for Safe Limited Speed with Door Monitoring, the
drive must be monitoring motion (SLS_In input is OFF) if the door is open
(DM_In is OFF). Make sure the door is closed before requesting an SLS Reset.

A Safe Limited Speed Reset results in a Door Monitoring fault if the door is open
(DM_In is OFF) when the reset is requested by a transition of the SLS_In input
from OFF to ON. A Door Monitor fault is a Stop Category fault that initiates
the configured Stop Category.

ATTENTION: Make sure that an open door does not result in a
hazardous situation.

If a Stop Category is initiated or a fault occurs while the drive is actively
monitoring Safe Limited Speed, door control remains unlocked. The safe
state of the SLS_In input can result in the door being unlocked.