Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual

Page 110

Advertising
background image

110

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Chapter 9

Safe Maximum Speed and Direction Monitoring

Max Speed, Max Accel, and
Direction Monitoring
Parameter List

Set these parameters to configure Safe Maximum Speed, Safe Maximum
Acceleration, and Safe Direction Monitoring.

Table 32 - Max Speed, Max Accel, and Direction Monitoring Parameters

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Feedback
Primary Feedback

Feedback Polarity

Defines the direction polarity for encoder 1.

Default:

Positive

Options:

Positive
Negative

Feedback
Secondary Feedback

Feedback Polarity

Defines the direction polarity for encoder 2.

Options:

Positive
Negative

Safe Max Speed
Change Safe
Maximum Speed
Configuration

Safe Maximum Speed
Configuration

Enable Maximum Speed Monitoring.

Default:

Maximum Speed Monitoring Not Enabled

Options:

Maximum Speed Monitoring Not Enabled
Maximum Speed Monitoring Enabled

Safe Maximum Speed
Limit

Defines the maximum speed limit that is tolerated if
Safe Maximum Speed (SMS) monitoring is enabled.

Default:

0

Range:

0…65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Safe Maximum Speed
Monitoring Stop
Behavior

Defines the Stop Category that is initiated in the event
of a SMS Speed fault.

Default:

Use Safe Torque-Off with Check for Standstill

Options:

Use Safe Torque-Off with Check for Standstill
Use Configured Stop Type

Safe Max Accel
Change Safe
Maximum
Acceleration
Configuration

Safe Maximum
Acceleration
Configuration

Enable Maximum Acceleration Monitoring.

Default:

Maximum Acceleration Monitoring Not Enabled

Options:

Maximum Acceleration Monitoring Not Enabled
Maximum Acceleration Monitoring Enabled

Safe Maximum
Acceleration Limit

Defines the Safe Maximum Acceleration (SMA) limit,
relative to encoder 1, of the system is being monitored.

Default:

0

Range:

0…65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Safe Maximum
Acceleration
Monitoring Stop
Behavior

Defines the Stop Category that is initiated in the event
of an SMA Acceleration fault.

Default:

Use Safe Torque-Off with Check for Standstill

Options:

Use Safe Torque-Off with Check for Standstill
Use Configured Stop Type

Safe Direction
Change Safe
Direction Monitoring
Configuration

Safe Direction
Monitoring
Configuration

Enable Safe Direction Monitoring.

Default:

Safe Direction Monitoring Not Enabled

Options:

Safe Direction Monitoring Not Enabled
Safe Direction Monitoring Enabled

Monitor Type

Defines the monitor type if Safe Direction Monitoring is
enabled.

Options:

Always
During Safe Limited Speed

Safe Direction

Defines the allowable direction if Safe Direction
Monitoring is enabled.

Default:

Positive

Options:

Positive
Negative

Jitter Tolerance

The position limit in encoder units tolerated in the
wrong direction when Safe Direction Monitoring is
active.

Default:

10

Range:

0…65,535 deg or mm
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter