Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual
Page 124
Advertising

124
Rockwell Automation Publication 2094-RM001C-EN-P - May 2013
Chapter 11
Safety Configuration Example
5. Click Refresh.
The Refresh command is used to apply the
current safety configuration.
6. Click Lock.
The [Safety Lock Status] parameter value
changes to Locked and this message appears as
confirmation.
If the configuration is already locked or
protected by a password, the command fails.
7. Click Unlock.
The [Safety Lock Status] parameter value
changes to Unlocked and this message
appears.
If the configuration is already unlocked or
protected by a password, the command fails.