60

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Chapter 6

Safe Stop and Safe Stop with Door Monitoring Modes

Safe Torque Off without Standstill Checking

When Safe Torque Off without Standstill Checking is initiated, motion power is
removed immediately and the configured Stop Delay [Maximum Stop Time]
begins. Door control logic is set to Unlock when the Stop Delay [Maximum Stop
Time] expires, regardless of speed.

Figure 15 - Timing Diagram for Safe Torque Off without Standstill Checking

(1) This signal is internal to the drive.
(2) DC_Out output shown configured as Power to Release. See

Door Control

on

page 64

for more information.

Stop Request

Stop Delay

Safe Torque-off

Active

Door Control
Output Unlock

Time

SS_Out Output

SS_In Input

Speed

Motion Power

(1)

DC_Out Output

(2)

TIP

All Stop Types require an encoder to be connected.