Safe Stop and Safe Stop with Door Monitoring Modes

Chapter 6

Standstill Speed and Position Tolerance

For Stop Categories that include Standstill Checking, you set the Standstill
Speed and Standstill Position Tolerance.

Standstill Speed is used to declare motion as stopped. The system is at standstill
when the speed detected is less than or equal to the configured Standstill Speed.
The [Standstill Speed] parameter defines the speed limit before the drive
determines standstill has been reached and the door control logic is set to
Unlock.

The [Standstill Position Window] parameter defines the position limit in
encoder 1 units that is tolerated after standstill has been reached. If the position
changes by more than the amount specified by the Standstill Position Tolerance,
after standstill has been reached and the door is unlocked, a Motion After
Stopped fault occurs. This type of fault results in the drive entering the safe state.

IMPORTANT

The [Standstill Speed] and [Standstill Position Window] parameters are not
used for Safe Torque Off without Standstill Checking configurations. Set these
parameters to zero.

IMPORTANT

Standstill detection relies on the encoder 1 signal. The encoder 2 signal is
used for fault diagnostics.