Safe Stop and Safe Stop with Door Monitoring Modes

Chapter 6

When Safe Stop 2 is executed, the Guard Gate drive output is on (status = 1)
until after standstill speed is reached or a fault occurs. Use this safe stop for
vertical load applications. The IGBT remains active, therefore follow the
examples on

page 57

to MAS before SS_Reset.

For Safe Stop 2, motion power is not removed when Standstill Speed is reached.

Figure 14 - Timing Diagram for Safe Stop 2

(1) This signal is internal to the drive.
(2) DC_Out output shown configured as Power to Release. See

Door Control

on

page 64

for more information.

IMPORTANT

For Safe Stop 2, the Logix Designer application must monitor the state of the
Axis.GuardStopRequestStatus tag. After the tag becomes active and stop
monitoring expires, the program must issue an MAS instruction. Successful
SS_Reset is required prior to restarting the machine.

SS_Out Output

SS_In Input

Stop Request

Stop Delay

Standstill Position and Standstill

Speed Monitoring

(drive remains enabled)

Deceleration
Tolerance

Standstill Speed

Speed

Stop Monitoring

Delay

Time

Motion Power

(1)

DC_Out Output

(2)