Page 31

Advertising
background image

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

31

Speed Monitoring I/O Signals

Chapter 4

When using a dual-channel complementary device, the normally-open input
must be connected to the second input, as shown in the illustration. For example,
if the door is open when the input is ON, the normally-open contact must be the
second input (Input 1).

Figure 4 - Safety Input Wiring Examples

Table 3 - IOD Connector Input Terminals

Short-circuits of the input loop to ground or 24V are detected. For dual-channel
inputs, cross loops are also detected.

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

Dual-channel
Equivalent
Safety Device

Dual-channel
Complementary
Safety Device

Single
Channel
Safety Device

Solid State
Safety Device

Drive

N/C
N/C

Input 1
Input 0

GND

OSSD2

OSSD1

Drive

Drive

Drive

Input 1
Input 0

Input 1
Input 0

24V_COM (IOD-18)

Input 1

Input 0

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

IMPORTANT

Cross wiring of Test Outputs to Inputs is not allowed. For example, do not
connect TEST_OUT_0 to Input 1 or TEST_OUT_1 to Input 0.

Function

Safe Stop
(SS_In)

Safe Limited
Speed
(SLS_In)

Door Monitoring
(DM_In)

Enabling Switch
Monitoring
(ESM_In)

Lock
Monitoring
(LM_In)

Input 0 = Channel 0

IOD-19

IOD-23

IOD-31

IOD-37

IOD-33

Input 1 = Channel 1

IOD-20

IOD-24

IOD-32

IOD-38

IOD-34