Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Chapter 8

Slave Modes for Multi-axis Cascaded Systems

Slave, Safe Limited Speed
Mode

When properly configured for Slave, Safe Limited Speed mode, the drive
performs the same functions as Safe Limited Speed mode as described on

page 71

.

However, the drive regards the Door Monitor input as a Door Control output
from an upstream axis, and performs a logical AND with its internal Door
Control signal to form the cascaded Door Control output. Door Monitoring,
Enabling Switch Monitoring, and Lock Monitoring functions are not allowed in
this mode.

For the door to unlock, all axes must be below safe limited speed.

Slave, Safe Limited Speed
Parameters

To configure the drive for Slave, Safe Limited Speed monitoring, set these
parameters in addition to the Slave, Safe Stop parameters listed on

page 91

. See

Multi-axis Connections

on

page 101

for details on configuring slave drives.

TIP

Only the middle and last drive in a multi-axis system can be configured for
slave modes.

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Safety
Change System
Configuration

System Configuration

Defines whether the drive is a single unit or if it occupies
a first, middle, or last position in a multi-axis cascaded
system.

Options:

Cascaded Middle Unit
Cascaded Last Unit

Operation Mode

Defines the primary operating mode of the speed
monitoring safety functions.

Default:

SafeStop-Safe Limited Speed

Input
Change Input
Configuration Type

Safe Limited Speed

Configuration for the Safe Limited Speed input
(SLS_In).

Default:

Solid State Device Equivalent 3 s

Safe Limited Speed
Change Safe Limited
Speed Configuration

Safe Limited Speed
Monitor Delay

Defines the Safe Limited Speed Monitoring Delay
between the SLS_In ON to OFF transition and the
initiation of the Safe Limited Speed (SLS) monitoring.

Default:

0

Range:

0…6553.5 s

Safe Speed Limit

Defines the speed limit that is monitored in Safe Limited
Speed (SLS) mode.

Default:

0

(1)

Range:

0…65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

(1) You must configure this parameter with a non-zero value in this mode.