Speed Monitoring I/O Signals

Chapter 4

When the Door Control output is configured as cascading (2Ch Sourcing), the
dual-channel bipolar output acts as two sourcing outputs capable of driving the
OSSD Door Monitor input (DM_In) of the next speed monitoring drive in the
cascaded chain. The DC_out output can also be used as a source for general
purpose inputs. In this configuration, the current is limited to 20 mA.

Figure 9 - Door Control Cascading Outputs

Only the wiring configurations shown below are supported for the Door Control
output.

Figure 10 - Door Control Output Wiring

(1) When wired as a source for a safety input, current is limited to 20 mA per output.
(2) For example, SmartGuard 600 controller, Guard I/O module.

Short-circuits of the output loop to ground or 24V are detected. For cascaded
outputs, cross loops are also detected.

DM_IN_CH0

DM_IN_CH1

DC_OUT_CH0

DC_OUT_CH1

Drive (Master)

Drive (Slave)

IOD-36

IOD-35

IOD-31

IOD-32

+

-

+

-

+

-

+

-

No

Load

Bi-polar

Load

Single-ended

Load

Door Status 2-Channel

Source

(1)

+24V DC

Door Control

Sourcing Output

Door Control

Sinking Output

+24V DC Common

Load

Load

Input Circuit

Input Circuit

IOD-35

IOD-35

IOD-36

IOD-36

IOD-35

IOD-35

IOD-36

IOD-36

(2)