Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual

Page 148

Advertising
background image

148

Rockwell Automation Publication 2094-RM001C-EN-P - May 2013

Appendix B

Parameter Data

Input
Change Input
Configuration Type

Door Monitor

Configuration for the Door Monitor input (DM_In).

Default:

Not Used

Lock Monitor

Configuration for the Lock Monitor input (LM_In).

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel

Safe Limited Speed

Configuration for the Safe Limited Speed input
(SLS_In).

Enabling Switch
Monitor

Configuration for the Enabling Switch input (ESM_In).

Safe Stop
Change Safe Stop
Configuration

Stop Category

Safe operating stop type selection. This defines the type
of Safe Stop that is performed if the Safe Stop function
is initiated by a stop type condition.

Default:

Safe Torque-Off

Options:

Safe Torque-Off
Safe Stop 1
Safe Stop 2

Enable Standstill Checking.
Automatically enabled for Safe Stop 1 and Safe Stop 2.

Default:

Standstill Checking Enabled

Options:

Standstill Checking Enabled
Standstill Checking Not Enabled

Safe Stop Monitor
Delay

Defines the monitoring delay between the request and
the Maximum Stop Time when the request for a Safe
Stop 1 or a Safe Stop 2 is initiated by an SS_In input ON
to OFF transition.
If the Stop Category is Safe Torque-Off with or without
Standstill Speed Checking, the Safe Stop Monitor Delay
must be 0 or an Invalid Configuration fault occurs.

Default:

0

Range:

0

6553.5 s

Deceleration
Reference Speed

Determines deceleration rate to monitor for Safe Stop 1
or Safe Stop 2.

Default:

0

Range:

0

65,535 rpm or mm/s

ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Maximum Stop Time

Defines the maximum stop delay time that is used when
the Safe Stop function is initiated by a stop type
condition.

Default:

0

Range:

0

6553.5 s

Deceleration
Tolerance

This is the acceptable tolerance above the deceleration
rate set by the [Deceleration Reference Speed]
parameter.

Default:

0

Range:

0

100% of Deceleration Reference Speed

Standstill Speed

Defines the speed limit that is used to declare motion as
stopped.
Not valid for Safe Torque-Off without Standstill
Checking.

Default:

0.001

Range:

0.001

65.535 rpm or mm/s

ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Standstill Position
Window

Defines the position limit window in encoder 1 degrees
or mm that is tolerated after a safe stop condition has
been detected.
Not valid for Safe Torque-Off without Standstill
Checking.

Default:

10

Range:

0

65,535 degrees (360° = 1 revolution) or mm

ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Safe Limited Speed
Change Safe Limited
Speed Configuration

Safe Limited Speed
Monitor Delay

Defines the Safe Limited Speed Monitoring Delay
between the SLS_In ON to OFF transition and the
initiation of the Safe Limited Speed (SLS) monitoring.

Default:

0

Range:

0

6553.5 s

Safe Speed Limit

Defines the speed limit that is monitored in Safe Limited
Speed (SLS) mode.

Default:

0

Range:

0

65,535 rpm or mm/s

ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Table 41 - Configurable Parameters and Settings (continued)

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)