Chapter

11

Safety Configuration Example

This configuration example guides you through the basic steps required to
program an application that uses some of the safety functions. The other chapters
of this manual provide detailed information on the operation of each safety
function.

Example Application

This example application uses the following basic configuration in a single-axis
system.

Safe Stop (SS) enabled with an E-stop button.
Safe Limited Speed (SLS) initiated with a 2NC contact switch.
Control & monitoring of door safety interlock switch (TLS 3 GD2)

configured as Power to Release.

A Reset button with 1 NO contact.
One encoder connected with Sin/Cos output signal and resolution of

1024 cycles per revolution.

A configured Safe Maximum Speed (SMS) limit.

Topic

Page

Example Application

121

Use the Initial Safety Main Tab Commands

123

Configure the Safety Tab Parameters

126

Feedback Tab Settings

127

Configure the Input Tab Parameters

128

Configure the Safe Stop Tab Parameters

129

Configure Safe Limited Speed Tab Parameters

130

Configure Safe Max Speed Tab Parameters

131

IMPORTANT

After replacing a 2094-xx02x-M0x-S1 safe-speed control module, the safety
configuration (web page) can be from the previous control module of the
same IP address. To correct this condition, go to Internet Explorer/Tools/
Internet Options and under Browsing history, click Delete to delete temporary
files, cookies, and web form information.