Safe Limited Speed (SLS) Modes

Chapter 7

Speed Hysteresis

The [Safe Limited Speed Hysteresis] parameter provides hysteresis for the
SLS_Out output when the drive is configured for SLS Status Only and Safe
Limited Speed monitoring is active. The SLS_Out output is turned ON if the
speed is less than the Low Threshold [(Speed Hysteresis/100) x Safe Speed
Limit]. The SLS_Out output is turned OFF when the speed is greater than or
equal to the configured [Safe Speed Limit].

The SLS_Out output remains OFF if Safe Limited Speed monitoring begins
when the detected speed is less than the configured Safe Speed Limit but greater
than or equal to the Low Threshold [(Speed Hysteresis/100) x Safe Speed
Limit].

The SLS_Out output is held in its last state when the speed is less than the
configured Safe Speed Limit and the speed is greater than or equal to the Low
Threshold [(Speed Hysteresis/100) x Safe Speed Limit].

SLS Status Only Parameter
List

To configure the drive for Safe Limited Speed Status Only monitoring, set these
parameters in addition to the Safe Stop parameters listed on

page 66

.

Table 26 - SLS Status Only Parameters

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Safety
Change System
Configuration

Operation Mode

Defines the primary operating mode of the speed
monitoring safety functions.

Setting:

SafeStop-Safe Limited Speed Status Only

Input
Change Input
Configuration Type

Safe Limited Speed

Configuration for the Safe Limited Speed input
(SLS_In).

Default:

Not Used

(1)

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel

Safe Limited Speed
Change Safe Limited
Speed Configuration

Safe Limited Speed
Monitor Delay

Defines the Safe Limited Speed Monitoring Delay
between the SLS_In ON to OFF transition and the
initiation of the Safe Limited Speed (SLS) monitoring.

Default:

0

Range:

0…6553.5 s

Safe Speed Limit

Defines the speed limit that is monitored in Safe Limited
Speed (SLS) mode.

Default:

0

Range:

0…65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Safe Limited Speed
Hysteresis

Provides hysteresis for SLS_Out output when Safe
Limited Speed monitoring is active.

Default:

0

Range:

10…100% when [Operation Mode] =
SafeStop-SafeLimitedSpeedStatusOnly

(1) You must configure this parameter with a non-zero value in this mode.