Chapter 6

Safe Stop and Safe Stop with Door Monitoring Modes

Lock Monitoring

If Lock Monitoring is enabled, the Lock Monitoring input (LM_In) must be in
the ON state any time the Door Control output (DC_Out) is in the Lock state,
except for the 5 seconds following the DC_Out output’s transition from the
Unlocked state to the Locked state. If the LM_In input is not ON during this
time, a Lock Monitoring fault occurs. The LM_In input must be OFF when the
DM_In input transitions from ON to OFF (the door opens).

A Lock Monitoring fault is a Stop Category fault that initiates the configured
Stop Category.

Safe Stop Parameter List

To configure the drive for Safe Stop mode, set these parameters in addition to the
General and Feedback parameters listed on

page 48

and

page 54

.

TIP

Not all Safe Stop configuration parameters require configuring for each Safe
Stop category.

Table 20 - Safe Stop Parameters

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)

Safety
Change System
Configuration

Operation Mode

Defines the primary operating mode of the speed
monitoring safety functions.

Setting:

SafeStop

Input
Change Input
Configuration Type

Safe Stop

Configuration for Safe Stop input (SS_In).

Default:

Dual Channel Equivalent

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel