Safe Stop and Safe Stop with Door Monitoring Modes

Chapter 6

Safe Stop
Change Safe Stop
Configuration

Stop Category

Safe operating stop type selection. This defines the type
of Safe Stop that is performed if the Safe Stop function
is initiated by a stop type condition.

Default:

Safe Torque-Off

Options:

Safe Torque-Off
Safe Stop 1
Safe Stop 2

Enable Standstill Checking.
Automatically enabled for Safe Stop 1 and Safe Stop 2.

Default:

Standstill Checking Enabled

Options:

Standstill Checking Enabled
Standstill Checking Not Enabled

Safe Stop Monitor
Delay

Defines the monitoring delay between the request and
the Maximum Stop Time when the request for a Safe
Stop 1 or a Safe Stop 2 is initiated by an SS_In input ON
to OFF transition.
If the Stop Category is Safe Torque-Off with or without
Standstill Speed Checking, the Safe Stop Monitor Delay
must be 0 or an Invalid Configuration fault occurs.

Default:

0

Range:

0…6553.5 s

Deceleration
Reference Speed

Determines deceleration rate to monitor for Safe Stop 1
or Safe Stop 2.

Default:

0

Range:

0…65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Maximum Stop Time

Defines the maximum stop delay time that is used when
the Safe Stop function is initiated by a stop type
condition.

Default:

0

Range:

0…6553.5 s

Deceleration
Tolerance

This is the acceptable tolerance above the deceleration
rate set by the [Deceleration Reference Speed]
parameter.

Default:

0

Range:

0…100% of Deceleration Reference Speed

Safe Stop
Change Safe Stop
Configuration

Standstill Speed

Defines the speed limit that is used to declare motion as
stopped.
Not valid for Safe Torque-Off without Standstill
Checking.

Default:

0.001

Range:

0.001…65.535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Standstill Position
Window

Defines the position limit window in encoder 1 degrees
or mm that are tolerated after a safe stop condition has
been detected.
Not valid for Safe Torque-Off without Standstill
Checking.

Default:

10

Range:

0…65,535 degrees (360° = 1 revolution) or mm
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter

Safety
Change System
Configuration

Door Control Output

Defines the lock and unlock state for door control output
(DC_Out).
Any Door Control Output option can be used for a
single-axis system or for the last unit in a multi-axis
system. The first and middle units of a multi-axis system
must be configured as 2 Channel Sourcing.

Default:

Power to Release

Options:

Power to Release
Power to Lock
2 Channel Sourcing

Enable Lock
Monitoring

Lock Monitoring can be enabled only when the drive is a
single unit or the first unit in a multi-axis system as set
in [System Configuration].

Default:

Lock Monitoring Not Enabled

Options:

Lock Monitoring Not Enabled
Lock Monitoring Enabled

Input
Change Input
Configuration Type

Lock Monitor

Configuration for the Lock Monitor input (LM_In).

Default:

Not Used

Options:

Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel

Table 20 - Safe Stop Parameters (continued)

Tab

Parameter Name

Description

Values
(Safety Configuration Tool)