Reset input (reset_in) – Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual
Page 34
Advertising

34
Rockwell Automation Publication 2094-RM001C-EN-P - May 2013
Chapter 4
Speed Monitoring I/O Signals
Reset Input (Reset_In)
The Reset input is for reset and monitoring of the safety circuit. The reset input
can be configured for automatic, manual, or manual monitored reset types.
Wire the reset input terminal (IOD-26) to the 24V DC input terminal,
(IOD-25), depending on the configured reset type, as shown.
Figure 5 - Reset Input Configurations
Manual
Manual
Monitored
Reset
Reset
RESET_IN
RESET_IN
IOD-25
IOD-26
IOD-25
IOD-26
IMPORTANT
If you configure the drive for automatic reset, wiring of the reset input
terminal (IOD-26)
is not required.