Safe Stop and Safe Stop with Door Monitoring Modes

Chapter 6

Configuration

You configure the type of door control for each Safe Speed Monitor Option
module in the system.

A single or last drive in a cascaded system can be configured for any Door Output
Type setting. For example, choose 2 Ch Sourcing to connect to a safety
programmable controller input. The first or middle drive in a cascaded system
must be configured as 2 Ch Sourcing.

Effect of Faults

These fault conditions affect the integrity of the DC_Out output and force the
DC_Out output to its safe state (OFF) regardless of the status of door control
logic:

DC Out fault
Invalid Configuration fault
Internal Power Supply or MPU faults

For fault conditions where the DC_Out output can maintain its integrity, both
door control logic and the DC_Out output hold last state. If hold last state
cannot be maintained, faults can turn the DC_Out output OFF.

[Door Control Output] Settings

DC_Out Status and Lock State

Single and Last Units

First and Middle Units

Power to Release

Not valid

ON = Door is unlocked.
OFF = Door is locked.

Power to Lock

Not valid

ON = Door is locked.
OFF = Door is unlocked.

Cascading
(2 Ch Sourcing)

Cascading
(2 Ch Sourcing)

ON = Door is unlocked.
OFF = Door is locked.

ATTENTION: When the DC_Out output is configured as Power to Lock, the safe
state and faulted state is Unlocked. Make sure that this possibility does not
create a hazard.

ATTENTION: If a fault occurs after Standstill Speed has been reached, door
control remains unlocked.

ATTENTION: If a fault occurs while the door is unlocked, it can remain
unlocked. Make sure that this possibility does not create a hazard.