CHAPTER 2 • CONNECTING POWER AND SURGE PROTECTION

35

Note

Do not strip the service end of the cable until after it has been routed through con-
duit. The cable should be one continuous run without any splices.

Use the steps below to land the sensor cables:
1 After routing your SmartSensor 6-conductor cable into the cabinet, carefully strip back

the cable jacket and shielding on the service end of the cable.

2 Open the insulation displacement connectors on the plug by inserting a small screw-

driver into each square slot and rocking it back.

3 Insert the wire leads into the bottom side of the plug-in terminal according to the color

code shown in Table 2.1 and Figure 2.8. Make sure the wires are completely inserted

in the terminal.

4 Close the insulation displacement connector by reinserting the screwdriver into the

square slot and rocking it forward. The plug-in terminals will automatically complete

the electrical connection. There is no need to manually strip the insulation on the end

of each wire.

There are two measures in place to ensure that the plugs are always returned to their correct

terminal block sections.

˽

First, for visual confirmation, one part of the plug is blue (see Figure 2.8) and must be

visually matched up to a blue terminal block. The location of the blue piece rotates in

the different plugs and terminal block sections: in the first, the first block is blue, in the

second, the second is blue, etc.

˽

Second, the plugs are keyed (see the blue piece in Figure 2.8) so they will only fit into

their correct terminal block sections.

Wire Color

Signal

Red (PWR)

DC+

Black (GND)

DC-

White with Blue stripe (485+)

Control bridge 485+ (port1)

Blue (485-)

Control bridge 485 - (port 1)

White with Orange stripe (485+)

Data bus 485+ (port 2)

Orange (485-)

Data bus 485- (port 2)

Bare metal (DRN)

Drain

Table 2.1 – Cable Wiring Color Code