Voltage transformation ratio: Primary and secondary voltage programming. The product of

the primary value and the primary current must be the same as or less than 20,000,000. The
value of the primary, depending on the fullscale of the equipment, must be between 1 and the
corresponding value from the following table:

Full-scale

Maximum value.

110V

99.999

250V

70.000

275V

70.000

300V

70.000

500V

40.000

Current transformation ratio: This is the device primary current value. Value may be

between 1 and 10,000 A. The secondary current is 5A in the CVM-96.

Period: This is the maximeter integration period and can vary between 1 and 60 minutes.

Window type: Type of window used to save the maximeter value, this can be fixed or sliding.

Unit: The maximum demand can be calculated with active power III, apparent power III,

current III or current by phase depending on the device.

Maximeter reset: When the button is pressed, the device maximeter resets to zero.


Selecting the type of voltage calculated.


Configuration of the "backlight" disconnection. The value should be between 0 and 99

seconds.


Use this selector to configure the type of distortion the device will calculate.


On clicking the button the energy counters on the device will reset to zero.