CIRCUTOR PowerStudio Series User Manual

Page 151

Advertising
background image

PowerStudio

User Manual 151

-

Block sync P: Synchronized with the company's maximeter, by means of synchronisation
pulses that occur at the beginning of each period.

-

Block sync T: Synchronized with the company's maximeter, by means of a synchronisation
pulse. From this the equipment calculates the beginning and end of each period based on
an internal clock. When it receives a new synchronisation pulse it will readjust and again
synchronise.

-

Rolling: Without synchronisation with the company's maximeter, using a sliding window.

-

Thermal: Without synchronisation with the company's maximeter, using a sliding window
and simulating the response of the thermal exponential function of the mechanical
counters.

Select the operating mode for controlling the relays, two

possibilities: predictive control or control by level. This parameter can only be configured when one of
the types of integration with synchronisation is selected, the types of integration without synchronisation
control will be by level. The control type will depend on the relay configuration.

Only in predictive control. The connection/disconnection type is

selected. The types are:


-

C. cyclic: Cyclic, the relays that have been operating the longest disconnect first.

-

C. lineal: Lineal, where connection or disconnection is done by priorities, relay 1 being the
first to disconnect.

Only in predictive control. Value of the power contracted for the

installation.

Only in predictive control. Minimum waiting time before

reconnecting a relay.

Only in predictive control. Time to adapt the controller response

time to the characteristics of the installation.

The number of relays to be used in the installation

is selected.

Only in predictive control. It will only be possible to choose between the two status

modes of the contract.

Only in predictive control. Value of the power contracted for each

of the relays.