Depending on the version connected, programming of the voltage transformation ratio can be

disabled.

Voltage transformation ratio: Primary and secondary voltage programming. The product

between the primary value and the primary current must be the same as or less than
20,000,000. The value of the primary, depending on the fullscale of the unit, must be between
1 and the corresponding value from the following table:

Fullscale background

Maximum value.

110V

99.999

250V

70.000

275V

70.000

300V

70.000

500V

40.000

Current transformation ratio: This is the device primary current value. Value may be

between 1 and 10,000 A. The secondary current is 5A in the CVM-96.

Period: Maximeter integration period, which can vary between 1 and 60 minutes.

Window type: Type of window used to save the maximeter value, which can be fixed or

sliding.

Unit: The maximum demand can be calculated with active power III, apparent power III,

current III or current by phase depending on the device.

Maximeter reset: Press the button to reset the maximeter to zero.


Selecting the type of voltage calculated.


Configuration of the "backlight" disconnection. The value should be between 0 and 99

seconds.