15 rrm-c, 16 tagreader, Rrm-c – CIRCUTOR PowerStudio Series User Manual

Page 287: Tagreader

Advertising
background image

PowerStudio

User Manual 287

RCPD

RCTD

RCPM

RCTM

RGU-10 RA

X

X

X

X


Pre-alarm trigger output status

Value

Not enabled

0

Enabled

1

Locking output status

Value

Not locked

0

Locked

1

Coil trigger output status

Value

Not Tripped

0

Tripped

1

Status of the device

Value

Start

0

Rest

1

Earth differential trigger locking

2

Earth differential trigger waiting

3

Circuit breaking trigger locking

4

Circuit breaking trigger waiting

5

Toroid disconnected

6

External input enabled

7

Remote trigger

8

Test trigger

9

Manufacturing mode

10

Calibration mode

11

To carry out a channel reset on the RGU-10 devices the RST variable must be forced to value 0.

To carry out a remote triggering of the channel the RST variable should be forced to the value 1.


2.1.11.15 RRM-C

Reconection counter

No. of reconnections selected

Time between
reconnections

Device status

RC

RN

RT

ST

RRM-C

X

X

X

X

Device status

Value

Unknown

65535

Connected

0

Locked

1

External trigger

2

Residual current device trigger

4

Communication trigger

8

External and communication trigger

10

On RRM-C devices the device status can be forced to 16 to reset it, or to 17 trigger the device

externally.

2.1.11.16 TAGREADER


Tag

TAG

Time

TIME