CIRCUTOR PowerStudio Series User Manual

Page 96

Advertising
background image

PowerStudio PowerStudio

96 User Manual

Voltage transformation ratio: Primary and secondary voltage programming. The product of

the primary value and the primary current must be the same as or less than 20,000,000. The
value of the primary, depending on the fullscale of the equipment, must be between 1 and the
corresponding value from the following table:

Full-scale

Maximum value.

110v

99.999

275v

70.000

300v

70.000

500v

40.000


Current transformation ratio: This is the device primary current value. Value may be

between 1 and 10,000 A. The secondary current is 5A in the CVM-96.

Period: Is the maximeter integration period can vary between 1 and 60 minutes.

Unit: The maximum demand can be calculated with active power III, apparent power III,

current III or current by phase depending on the device.

Maximeter reset: When the button is pressed, the device maximeter resets to zero.


Use this selector to configure the type of distortion the device will calculate.


Clicking the button will reset the energy counters on the device to zero.


This section shows the configuration of the device relay outputs, configuration is possible with

the required values.

Variable: The parameters associated with the relay are indicated in this field. The output is

programd as an alarm, and can control any of the parameters measured by the CVM-96. The
maximum and minimum alarm unit values are indicated in brackets.

Max: This box indicates the maximum value to be controlled.

Min: This box indicates the minimum value to be controlled.

Delay: Alarm delay in seconds. The maximum value is 9999 seconds.

Advertising