2 displaying values, 1 rgu-10, Displaying values – CIRCUTOR PowerStudio Series User Manual

Page 227: Rgu-10

Advertising
background image

PowerStudio

User Manual 227

Switch

Circuit breaker

Circuit breaker + trigger coil

Polarity of the locking relay output.
Operation mode.

1.58.2 Displaying values

1.58.2.1.1 RGU-10


The RGU-10 device will show the following screen values:


Where:

1. Protection status:

Not tripped

Tripped.

2. Additional information on the protection status.
3. Differential current value detected in the channel trigger. This information will

only be visible when the channel is tripped.

4. Pre-alarm status:

Disabled

Pre-alarm enabled

5. Additional information on the status of the pre-alarm.
6. Additional information on the pre-alarm reconnection. This will only appear

when automatic reconnection of the pre-alarm is enabled.

7. Information about the configured trigger current threshold
8. Information about the configured trigger time.
9. Adjustment button. Displays channel information and allows some parameters

to be modified.

10. Reset button. If the channel is not triggered, the button will remain disabled.

Push the button to restart the channel.

11. OFF button. Enables remote triggering of the channel to be made. If the

channel is tripped the button will remain disabled.

12. Instantaneous differential current value. If the value exceeds the limits of the

values bar, both over or under, an arrow below the value will indicate this.

13. Trigger threshold value configured for the channel
14. Pre-alarm value configured for the channel.