Iii-4.7 mono (monoflop (no. 66)) 110, Mono 110, Monoflop 110 – West Control Solutions KS98-1 User Manual

Page 110: Iii-4.7 mono (monoflop (no. 66)), Inputs/outputs

Advertising
background image

III-4.7

MONO (monoflop (No. 66))

The function generates a positive pulse of length Ti

1

at output z1, when a positive flank at trigger input d1 is detected.

It generates a positive pulse of length Ti

2

at output z3, when a negative flank at trigger input d2 is detected.

Pulse duration Ti

1

is adjusted either as parameter Ti1 or read in via inputs Ti1. The origin of pulse duration is selected

via parameter Mode 1. The duration of an output pulse is matched to the new values with changes at inputs Ti1/Ti2.
With input values Ti1/Ti2 ß 0, the pulse is output for the duration of one scanning cycle.

The function is re-triggerable. I.e., if a new trigger condition is detected during a pulse output, the remaining pulse
time to be output is prolonged to a full pulse length.

The pulse duration accuracy is dependent of the sampling time, which is assigned to the function.

Example:

Ti = 0,9s for assignment to

- sampling interval 100ms means that the signal is output during = 0,9s.
- Sampling interval 200ms means that the signal is output during = 1,0s.
- Sampling time 400ms means that the signal is output during = 1,2s.
- Sampling interval 800ms means that the signal is output during = 1,6s.

Inputs/outputs

Digital inputs

d1

Triggerinput: Pulse at

z1 and not z1 with positive flank 0 r 1

d2

Triggerinput: Pulse at

z3 and not z3 with positive flank 1 r 0

Analog inputs

Ti1

Pulse duration Ti

1

[s] of the pulse generated by

d1, when Mode 1 = Para.Ti1.

Ti2

Pulse duration Ti

2

[s] of the pulse generated by

d2, when Mode 2 = Para.Ti2.

Digital outputs

z1

Positive pulse of length Ti

1

, when a positive flank at input

d1 was detected.

not z1

Negative pulse of length Ti

1

, when a positive flank at input

d1 was detected.

z3

Positive pulse of length Ti

2

, when a positve flank at input

d2 was detected.

not z3

Negative pulse of length Ti

2

, when a positive flank at input

d2 was detected.

9499-040-82711

Logic functions

MONO (monoflop (No. 66))

III-110

Ti1

d1

Ti2

d2

Ti1

Mode1

Ti2

Mode2

T1

T1

T1

T2

T2

T2

z1

not z1

z3

not z3