West Control Solutions KS98-1 User Manual

Page 162

Advertising
background image

w

With a positive edge at the

store input, the values applied to the signal inputs are stored as parameters y1

and

y2, i.e. as output values.

w

When an ALLP is connected at inputs x1 and x2, its limits L1 and H1 are used for parameter adjustment.

With digital input

lock set, no values can be changed. With digital input hide set, the operating page cannot be

displayed during operation. A 16-digit text for the display header can be adjusted user-specifically via the engineering
tool. The same is applicable for further texts for identification of value and unit.

a

Values of the used analog inputs are stored as parameter values when detecting a positive edge at the
store- input. This input should be activated only with relevant changes of the input values. Too frequent

storing operations may lead to the destruction of the EEPROM! (

r page 311)

Inputs/outputs

Digital inputs:
hide

Display suppression (with

hide = 1 the operating page is not displayed).

lock

Adjustment blocking (with

lock = 1 these values cannot be adjusted by means of keys ID).

Analog inputs:
x1 / x2

Process values to be displayed as values (default = 0)

x3 / x4

Process values to be displayed as bargraph (default = 0)

Analog outputs:
y1 / y2

Valid process values

Parameter and configuration data

Parameter

Description

Range

Default

Y1 / Y2

Start values at power-on

-29999...999 999

0

Configuration Description

Values

Default

Disp1
Disp2

Function of

numeric

display 1 and

2

display x1 / x2, value adjustable

disp+adj

only display x1 / x2

display

t

x1 / x2 = empty

empty

Dp1 / Dp2

Digits behind the decimal point in numeric display 1 / 2

0 ... 3

0

Typ

Position of

bargraphs

Both bargraphs horizontal

horizont

t

Both bargraphs vertical

vertical

X3

0

Display scaling bargraph 1, 0% (left or bottom end)

-29999...999 999

0

X3 100

Display scaling bargraph 1, 100% (right or upper end)

-29999...999 999

100

X3 mid

Display scaling bargraph 1, start value (middle)

-29999...999 999

0

X4

0

Display scaling bargraph 2, 0% (left or bottom end)

-29999...999 999

0

X4 100

Display scaling bargraph 2, 100% (right or upper end)

-29999...999 999

100

X4 mid

Display scaling bargraph 2, start value (middle)

-29999...999 999

0

9499-040-82711

Visualization

VBAR ( bargraph display (No. 97) )

III-162

Advertising