Iii-20.2 f_inp (frequency/counter input) 302, F_inp 302, Frequency counter input (f_inp) 302 – West Control Solutions KS98-1 User Manual

Page 302: Iii-20.2 f_inp (frequency/counter input)

Advertising
background image

III-20.2

F_Inp (frequency/counter input)

The frequency/counter input plugs into the modular options card C.The F_INP is used for configuration and parameter
setting of input

F_INP. Input calculation is fixed to once per time slot.

Digital inputs:
reset a

1 = the value for

Inp_a is reset to 0.

stop a

1 = the instantaneous value for

Inp_a remains unchanged.

reset b

1 = the value for

Inp_b is reset to 0.

stop b

1 = the instantaneous value for

Inp_b remains unchanged.

Digital outputs:

slotid

0 = correct module fitted
1 = wrong module fitted

fail

1 = inserted module is detected, but no communication to the module.

z_a

signal status of HW input a

z_b

signal status of HW input b

ov_a

1 = frequency at HW input a exceeds the maximum permissible 20kHz

ov_b

1 = frequency at HW input b exceeds the maximum permissible 20kHz

Analog outputs
Inp_a

output value for channel a

Inp_b

output value for channel b

Configuration

Description

Values

Default

Func_a

DigInputr con-trol input

0

1

Count_1 r up counter

1

Count_2

r up/down counter

2

Count_3

r up/down counter with direction signal

3

Count_4

r quadrature signal

4

Frequenzr fre-quency measuring

5

Func_b

DigInputr con-trol input

0

1

Count_1

r up counter

1

Frequenz

r frequency measuring

5

Time

for frequency measuring in seconds

0,1...20

10

9499-040-82711

Modular I/O - extension-modules

F_Inp (frequency/counter input)

III-302

stop a

0000

reseta

Inp_a

stop b

0000

resetb

Inp_b

a

b

Advertising