Iii-6.8 time2 ( timer (no. 70) ) 133, Timer2 133 – West Control Solutions KS98-1 User Manual

Page 133

Advertising
background image

III-6.8

TIME2 ( timer (No. 70) )

The function timer2 can only be used with real-time clock. With a positive flank at

start, TIMER2 is started and

output

z1 is switched to 1 after elapse of time TS and reset to 0 after elapse of time TE.

Example:

TS.D = 2, TS.H = 1, TS.Mi = 30 TE.D = 0, TE.H = 2, TE.Mi = 2

After the change from 0 to 1 at input

start, output z1 is set to 1 after 2 days, 1 hour and 30 seconds and reset to

0 after 2 hours and 2 seconds. Cyclic switching operations can be realized by feed-back of the

end output to the

start input.

Inputs/outputs

Digital inputs
disabl

= 1 suppresses the switching operation.

reset

= 1 finishes an instantaneously running switching operation immediately.

start

= 1 switch-on duration start

Digital outputs
z1

= 1 switching operation running

end

= 1 switching operation end

Analog output
Week-D

indicates the actual weekday ( 0...6 = Su...Sa)

Parameters:

Parameter

Description

Range

Default

TS.D

Switch-on delay day

0...255

0

TS.H

Switch-on delay hour

0...23

0

TS.Mi

Switch-on delay minute

0...59

0

TE.D

Switch-on duration days

0...255

0

TE.H

Switch-on duration hours

0...23

0

TE.Mi

Switch-on duration minutes

0...29

0

* 1) with the engineering tool broken rational numbers can be used; however only the integral

portion is taken over!

Time functions

9499-040-82711

III-133

TIME2 ( timer (No. 70) )

disabl
start
reset

end

z1
Week-D

TS.D
TS.H
TS.Mi

TE.D
TE.H
TE.Mi

t