Change mode (ramp/step)
If the shall change in a step or ramp is determined by a
parameter (
Wmode) valid for all segments of a recipe (de-
fault: ramp).
Ramp: The changes linearly from the start (end value of
previous segment) to the end value of the relevant seg-
ment in time
Tp. For the first segment, the following gra-
dient is applicable: (
Wp1 - Wp0) / Tp1
Step: The goes to value
Wp immediately at segment start
and maintains it during segment time
Tp.