III-10 Communication

ISO 1745

In total, max. 20 L1READ and L1WRIT functions can be configured (blocks 1...20 ), any combination of functions is pos -
sible. Any number of data can be used in the functions.

III-10.1

L1READ ( read level1 data(No. 100) )

General

Any 7 analog process values (x1...x7) and any 12 digital status informations (d1...d12) of the engineering are composed into a
data set for the digital interface. The digital interface can read the data set as a complete block with code 00, function num-
ber 0, or the individual values with codes 01...09, function number 0.

Inputs/outputs

Digital inputs:
d1 ... d6

Digital process values, which can be read via interface (status byte 1). (Default = 0)

d7 ... d12

Digital process values, which can be read via interface (status byte 2). (Default = 0)

Analog inputs:
x1 ... x7

Analog process values, which can be read via interface. (Default = 0)

Engineering example

In the following example, several process data (process value, effective and control deviation) and controller statuses
(automatic/manual, Wint/Wext and y/Y2) are connected with the L1READ function block. Now, these data can be read
in a message via interface.

9499-040-82711

Communication

L1READ ( read level1 data(No. 100) )

III-169

Interface

x1

x7

...

Statusbyte1

Code 01

Code 02

Code

00

Code 03

Code 04

Code 05

Code 06

Code 07

Code 08

Code 09

6 5 4 3 2 1 0

d6

d1

...

Statusbyte2

6 5 4 3 2 1 0

d12

d7

...

Example for L1READ engineering