Iii-8.3 equal ( comparison (no. 42) ) 150, Comparison 150, Equal 150 – West Control Solutions KS98-1 User Manual
Page 150: Iii-8.3 equal ( comparison (no. 42) ), Inputs/outputs, Parameters

III-8.3
EQUAL ( comparison (No. 42) )
The function checks the two analog input values x1 and x2 for equality.
The values are equal, if the amount of their difference is smaller than oder equal to the preset tolerance.
Comparison conditions
z6
z5
z4
z3
z2
z1
x2 + Diff <
x1
1
1
0
0
0
1
x2 - Diff £ x1 £ x2 + Diff
1
0
1
0
1
0
x2 - Diff > x1
0
1
1
1
0
0
The tolerance can be adjusted either as parameter Diff (
Mode = Para.Diff) or
entered at analog input Diff (
Mode = Inp.Diff).
Inputs/outputs
Analog inputs
x1
1st input value to be compared
x2
2nd input value
Diff
Tolerance for comparison operations
Digital outputs
z1
z1= 1 with x2 + Diff < x1
z2
z2= 1 with x2 - Diff £ x1 £ x2 + Diff
z3
z3= 1 with x2 - Diff > x1
z4
z4= 1 with x2 + Diff ³ x1
z5
z5= 1 with x2 - Diff > x1 > x2 + Diff
z6
z6= 1 with x2 - Diff £ x1
No configuration parameters!
Parameters:
Parameter
Description
Range
Default
Mode
Tolerance source
Parameter
Diff
Para.Diff
t
analog input
Diff
Inp.Diff
Diff
Tolerance for compari-
son operation
0 ... 999 999
0
9499-040-82711
Limit value signalling and limiting
EQUAL ( comparison (No. 42) )
III-150
Mode
Diff
X1
X2
Diff
X1>X2
X1=<X2
X1=X2
X1<>X2
X1<X2
X1>=X2