Iii-8.3 equal ( comparison (no. 42) ) 150, Comparison 150, Equal 150 – West Control Solutions KS98-1 User Manual

Page 150: Iii-8.3 equal ( comparison (no. 42) ), Inputs/outputs, Parameters

Advertising
background image

III-8.3

EQUAL ( comparison (No. 42) )

The function checks the two analog input values x1 and x2 for equality.
The values are equal, if the amount of their difference is smaller than oder equal to the preset tolerance.

Comparison conditions

z6

z5

z4

z3

z2

z1

x2 + Diff <

x1

1

1

0

0

0

1

x2 - Diff £ x1 £ x2 + Diff

1

0

1

0

1

0

x2 - Diff > x1

0

1

1

1

0

0

The tolerance can be adjusted either as parameter Diff (

Mode = Para.Diff) or

entered at analog input Diff (

Mode = Inp.Diff).

Inputs/outputs

Analog inputs

x1

1st input value to be compared

x2

2nd input value

Diff

Tolerance for comparison operations

Digital outputs

z1

z1= 1 with x2 + Diff < x1

z2

z2= 1 with x2 - Diff £ x1 £ x2 + Diff

z3

z3= 1 with x2 - Diff > x1

z4

z4= 1 with x2 + Diff ³ x1

z5

z5= 1 with x2 - Diff > x1 > x2 + Diff

z6

z6= 1 with x2 - Diff £ x1

No configuration parameters!

Parameters:

Parameter

Description

Range

Default

Mode

Tolerance source

Parameter

Diff

Para.Diff

t

analog input

Diff

Inp.Diff

Diff

Tolerance for compari-
son operation

0 ... 999 999

0

9499-040-82711

Limit value signalling and limiting

EQUAL ( comparison (No. 42) )

III-150

Mode

Diff

X1
X2
Diff

X1>X2

X1=<X2

X1=X2

X1<>X2

X1<X2

X1>=X2

Advertising