Out4 and out5 288, Process outputs 4 and 5 288 – West Control Solutions KS98-1 User Manual

Page 288

Advertising
background image

III-18.3

OUT4 and OUT5 ( process outputs 4 and 5 (No. 119...120))

Functions OUT4 and OUT5 are used for process output OUT4 and OUT5 configuration and parameter setting. These two
relay outputs are always provided as standard. Function OUT4 is firmly allocated to block number 84, function OUT5 is
firmly allocated to block number 85. They are calculated firmly in each time slot.

With digital input

d1 used as signal source, it is switched to the relay output as specified in Mode. If analog input

x1 is used as signal source, switching from x0 to x100 is from 50% (hysteresis = 1%).

Inputs / outputs

Digital input:
d1

Standard signal with digital signal conversion

Analog input:
x1

Input signal with analog signal conversion

Configuration parameter:

Parameter

Description

Values

Default

Src

Signal source

Digital input

d1

Digital

t

Analog input

x1

Analog

Mode

Signal source action

direct/normally open

direct

t

invers/normally closed

inverse

x0

Analog input value

x1 at 0%

-29 999 ... 999 999

0

x100

Analog input value

x1 at 100%

-29 999 ... 999 999

100

9499-040-82711

Outputs

OUT4 and OUT5 ( process outputs 4 and 5 (No. 119...120))

III-288

HARDW

ARE

SOFTW

ARE

Relais

d1
x1

OUT4
OUT5

Src

x0

x100

Mode

Advertising