reset
Analog input

Mean goes to value 0 for the duration of the applied reset signal.

The stored values are deleted.

Example:
ValNo = 5 output Mean at reset:

x

1

=

x

x

x

x

x

Detection that no valid values are available is made. Value 0 is output at output

y1.

ValNo = 5 1st sample after reset:

x1=

55

x

x

x

x

Detection that only one valid valid value is available is made. The only valid value

y1 = 55 is available at output y1.

ValNo = 5 2nd sample after reset:

x1=

44

55

x

x

x

Detection that two valid values are available is made. The mean value of these valid values

y1 =49,5 is output at out-

put

y1.

After all memory cells with a value are occupied (ValNr = 5), with every sample a new input value is added, the at this
time oldest value subtracted and the result divided by ValNr. = 5. The input values are shifted (like with a shift regis -
ter).

Inputs/outputs

Digital inputs
disabl

The disable input interrupts sampling

reset

The reset input clears the memory and resets the mean value to 0.

sample

A positive flank (0 r 1) is used for sampling a new value.

Analog input
x1

Process value, of which the mean value is formed.

Digital output
ready

Display for an elapsed overall cycle

Analog output
Mean

Calculated mean value

Configuration:

Parameter

Description

Value

Default

ValNo

Number of values which can be aquired

1...100

100

Unit

Unit of time for “

Sample”

Seconds

sec

t

Minutes

min

Hours

h

Sample

Interval time for averaging

0,1...999 999

1

Signal converters

9499-040-82711

III-123

MEAN (mean value formation (No. 75))