Inputs/outputs, Configuration – West Control Solutions KS98-1 User Manual

Page 113

Advertising
background image

Inputs/outputs

Digital input

d1

This signal is output with a delay at output

z1 and negated at output not z1.

Analog inputs

T1

Delay time T1 [s], by which the positive signal of

d1 is delayed, when Mode = Inputs.

T2

Delay time T2 [s]

, b

y which the negativ

e signal o

f

d2 is delayed, when Mode = Inputs.

Digital outputs

z1

Delayed input signal

d1.

not z1

Inverted delayed input signal

d1.

Configuration:

Configuration Description

Range

Default

Mode

Source of delay times

parameters T1 and T2

Parameters

r

Inputs T1 and T2

Inputs

The pulse duration accuracy is dependent of the time group to which the function is assigned.
It is an integer multiple of the sampling interval adjusted for this block (100, 200, 400, 800ms).

Example:

T1 = 0,7s with assignment to

- sample time 100ms means, delay time of the positive flank is 0,7s.
- sample time 200ms means, delay time of the positive flank is 0,8s.
- sample time 400ms means, delay time of the positive flank is 1,2s.
- sample time 800ms means, delay time of the positive flank is 1,6s.

Example with different delay time T1 and T2

Logic functions

9499-040-82711

III-113

TIME1 (timer (No. 69))

Input

Output

Output

Output

Output

Output

Output

d1

z1

z1

z1

z1

z1

z1

T1 = 1
T2 = 1

T1 = 1
T2 = 2

T1 = 1
T2 = 3

T1 = 1
T2 = 4

T1 = 2
T2 = 1

T1 = 3
T2 = 1

T1

T1

T1

T2

T2

T1

T2

T2

T1

T1

T2

T2

T1

T1

T2

T2

T1

T2

T1

T1

T2

T1

T2

T2

Fig. 111

Advertising