Iii-6.3 lag1 ( filter (no. 52)) 128, Filter 128, Lag1 128 – West Control Solutions KS98-1 User Manual

Page 128

Advertising
background image

III-6.3

LAG1 ( filter (No. 52))

Dependent of control input reset, input variable x1 is passed on to output y1 with delay (reset= 0) or without delay (re -
set = 1). Delay is according to a 1st order e-function ( 1st order low pass ) with time constant T(s). The output variable
for reset= 0 is calculated according to the following equation:

( )

(

)

( )

y t

T

T

t

y t

t

t

T

t

x t

s

s

s

s

1

1

1

=

+

Ч

-

+

+

Ч

ts sampling interval

x1 (t)

instantaneous x1

T

time constant

x1(t-ts)

y1 after t

n ts

= ×

n

number of calculation cycles

y1(t-ts)

previous y1

The complex transfer function is:

( )

F p

p t

=

+ ×

1

1

Inputs/outputs:

Digital input

reset

= 0 means that input signal x1 is output without delay at output y1.
= 1 means that input signal x1 is output at output y1 according to the calculated e-function.

Analog input
x1

Input variable to be calculated

Analog output
y1

Delayed output variable

Parameter:

Parameter

Description

Range

Default

T

Time constant in s

0...199999

1

No configuration parameters!

9499-040-82711

Time functions

LAG1 ( filter (No. 52))

III-128

T

reset

x1

y1

Advertising