Can i/o extension, Power supply – West Control Solutions KS98-1 User Manual

Page 16

Advertising
background image

mA input

Range

Overall error

Resolution

0/4...20 mA

£ 40 mA

2

mA

Input resistance: 10

W

Break monitor:<2

mA (only for 4...20 mA)

Over range monitor: >22mA

U_INP High-impedance voltage input

(9407-998-0x221)

Range

Overall error

Resolution mV/Digit

-50...1500 mV

£ 1,5 mV

0,09

0...10 V

£ 10 mV

0,56

Characteristic: voltage-linear

Input resistance: >1G

W

Source resistance effect:

£ 0,25 mV/MW

Sensor monitoring: none

U_OUT Voltage output module

(9407-998-0x301)

Signal ranges: 0/2...10V, -10...10V configurable

Resolution: approx.. 5.4 mV/digit

Load:

³ 2 kW

Load effect :

£ 0.1%

I_OUT Current output module

(9407-998-0x311)

Signal ranges: 0/4...20mA, -20...20mA configurable by channel

Resolution: ca. 11

mA/Digit

Load:

£ 400 W

Load effect:

£ 0.1%/100W

DIDO Digital I/O Module
(9407-998-0x401)

Number of channels: 2 (configurable as input or output by channel)

Input

Current sink: to IEC 1131 Type 1)
Logic „0“: -3...5V, Logic „1“: 15...30V
Measurement cycle: 100 ms

Galvanic isolation : via opto-couplers

Nominal voltage: 24 VDC external
Input resistance: 5 k

W

Output

Grounded load (common positive control voltage)

Switch rating: 18...32 VDC;

£

70 mA

Internal voltage drop:

£

0.7 V

Refresh-Rate: 100 ms

Galvanic isolation : via opto-couplers

Protective circuit: thermal, switches off with overload.

F_INP Frequency/counter Module
(9407-998-0x411)

Current sink: to IEC 1131 Type 1
Logic „0“: -3...5V
Logic „1“: 15...30V

Galvanic isolation: via Opto-couplers

Nominal voltage: 24 VDC external

Input resistance: 12 k

W

Selectable functions:

w

Control input (2 channels)

w

Pulse counter (2 channels)

w

Frequency counter (2 channels)

w

Up/down counter (1 channel)

w

Quadrature counter (1 channel)

Frequency range:

£

20 kHz

Signal shape: any (square 1:1 with 20kHz)

Gate time: 0.1...20s adjustable (only relevant with frequency mea-
surement)

Influencing factors

Temperature effect:

£ 0,1%/10K

Supply voltage: negligible

Common mode interference: negligible up to 50 Vrms

Series mode interference: negligible up to 300 mVrms (TC),
30 mVrms (RT), 10 Vrms (U), 5 Vrms (F)

CAN I/O extension

The unit offers a port conforming to CANopen for connection of
the RM 200 system and of KS 800 or additional KS 98-1 units with
max. five CAN nodes.

+

Control inputs di1 and di2 are not available !

+

Modular option C is not available

Power supply

Dependent on version:

Alternating current

90...250 VAC

Frequency: 48...62 Hz

Power consumption: approx. 17,1 VA; 9,7 W (max. configuration).

Universal current 24 V UC

24 VAC, 48...62 Hz/24 VDC

Tolerance: +10...–15% AC 18...31.2 VDC

Power consumption AC: approx. 14.1 VA; 9.5

W

DC: 9,1 W (max. Configuration).

Technical data

9499-040-82711

I-16