Inputs/outputs for PIDMA

Digital inputs:
hide

Display suppression (with

hide = 1 the operating page is not displayed).

lock

Adjustment locking (with

lock = 1 the values are not adjustable. Function keys ID are not active).

inc

Increment for manual adjustment

dec

Decrement for manual adjustment

x f

Sensor error x1...x3

yp f

Sensor error Yp

a/m

0 = automatic 1 = manual

w/w2

0 = int./ext. 1 = W2

we/wi

0 = external setpoint 1 = internal setpoint

track

0 = tracking function off; 1 = tracking function on(r page 273, 262, 263)

y/y2

0 = output value Y1 = output value Y2

off

0 = controller switched on 1 = controller switched off

sm/hm

0 = soft manual 1 = hard manual

ostart

1 = self-tuning start r page

w stop

1 = effective setpoint freeze

gr off

1 = setpoint gradient suppression

rstart

1 = Start the setpoint ramp r the setpoint makes a step change towards the process value and goes to the
adjusted process value according to GRW+ (GRW-). The rising flank (0r1) is evaluated.

o-hide

1 = self-tuning page display suppression

oplock

Blockage of key H (with

oplock

= 1, switchover to manual by means of key H is not possible).

Digital outputs:
y1

Status of switching output Y1; 0 = off 1 = on

y2

Status of switching output Y2; 0 = off 1 = on

c fail

1 = controller in error handling

off

0 = controller switched off 1 = controller switched on

a/m

0 = automatic 1 = manual

y/y2

0 = output value Y 1 = output value Y2

we/wi

0 = external setpoint, 1 = internal setpoint

o run

Self-tuning running

o err

Error during self-tuning

xw sup

Alarm suppression with setpoint change

Analog inputs:
x1

Main variable x1

x2

Auxiliary variable x2

e.g. for ratio control

x3

Auxiliary variable x3

e.g. for 3-element control

Wext

External

OVC+

Override control + r page 269

OVC-

Override control - r page 269

Yp

Position feedback

Yhm

Output with hard manual

Yadd

Feed-forward control

Casc

Cascade input for controller cascade

ParNo

Only with CONTR+; required parameter set

Analog outputs:
Weff

Effective setpoint

X

Effective process value

Y

Effective output value

XW

Control deviation

W

Internal

Yout1

Output value yout1 (heating)

Yout2

Correcting variable yout2 (cooling; only with continuous controller with split-range behaviour r

CFunc=

splitRange)

Bl-no

Own block number

ParNo

Only with CONTR+; effective parameter set

9499-040-82711

PIDMA (Control function with particular self-tuning behaviour (No. 93)