West Control Solutions KS98-1 User Manual

Page 78

Advertising
background image

For controlling, we also need a controller (in Functions - Controllers > CONTR).

#

This controller should be positioned behind the input.

<

The same we do with the OUT4 and place him below the controller.

In the next step, we have to soft-wire the function blocks, in order to provide a connection from the input via the con -
troller to the output.

>

For this purpose, we can select the wiring mode (via
menu Edit Wiring or by a simple double-click). The
mouse pointer as an arrow is displayed.

We use it to draw a line from the tip of the AINP1
(red arrow right) output arrow to controller input ar-
row X1 by (means of the left key).

y

Accordingly, we draw a connection from controller po-
sitioning output Yout1 of the controller block to the
input arrow of output block OUT4.

All function blocks have still to be checked for correct parameter setting. AINP1 is set to 0-20mA as default, which is
OK to start with. OUT4 is relay to the first output. The controller default setting is “ continuous control”, we set it to
2-point in the field "CFUNC".

Building an engineering

9499-040-82711

II-78

Fig. 102

Advertising