I-9 instrument settings in the main menu 34, I-9.1 can-status 34, I-9.2 profibus-status 34 – West Control Solutions KS98-1 User Manual

Page 34: I-9.3 modc-status 34, I-9 instrument settings in the main menu, I-9.1 can-status, I-9.2 profibus-status, I-9.3 modc-status

Advertising
background image

I-9

Instrument settings in the main menu

I-9.1

CAN-Status

The CAN bus status with the connected units is displayed.

Value

Signification

1...42

Node number

NC

NoCheck: Node existence not checked so far / node not provided

Ck

Check: Node existence just being checked.

NR

NoResponse: No reply from this node, but node is required

OK

Ready: Node has replied and is identified

ES

EMStart:Node has provided an emergency message

NA

NotAvailable: Node status is unknown

PO

PreOperation: Node is in the PreOperational status.

Er

Error: Node is in error status

Op

Operational: Node is in Operational status.

NU

NotUsed: Node is not required by an own lib function.

Wa

Waiting: Lib function waits for identification of this node.

Pa

Parametrierung: Lib function just setting the node parameters

OK

Ready: Lib function has finished the parameter setting.

String

detemined node name

I-9.2

Profibus-Status

The Profibus status page provides information on the Profibus connection
status. The following error statuses are displayed:

• Bus access not successful
• Faulty parameter setting
• Faulty configuration
• No data communication

I-9.3

ModC-Status

The status page of the modular C card provides information on correct in-
stallation. Possible faulty installations are displayed:

• Difference of configured and fitted module type
• Power limits exceeded

Instrument settings in the main menu

9499-040-82711

I-34

CAN-Status

Advertising